Alpha/Beta Firmware Versions
Note: The final version of firmware 4.0 has been
released. You should not be using these alpha or beta versions anymore,
unless you have very special reasons to do so. Please use the regular
released version for the latest features and bug fixes.
Disclaimer: The firmware versions provided here are in alpha or beta
state. The possibility of bugs is not at all precluded. Use of any of these
items is completely at your own risk.
Firmware Image Files
Version |
PIC |
Date |
Size |
File |
Downloads |
4.0a2 |
P16F88 |
Jan 26, 2013 |
16207 |
gateway-4.0a2.hex |
522 |
4.0a3 |
P16F88 |
Jan 27, 2013 |
17042 |
gateway-4.0a3.hex |
438 |
4.0a4 |
P16F88 |
Feb 4, 2013 |
17153 |
gateway-4.0a4.hex |
424 |
4.0a5 |
P16F88 |
Feb 9, 2013 |
18119 |
gateway-4.0a5.hex |
470 |
4.0a6 |
P16F88 |
Jul 27, 2013 |
20599 |
gateway-4.0a6.hex |
424 |
4.0a7 |
P16F88 |
Sep 22, 2013 |
21524 |
gateway-4.0a7.hex |
417 |
4.0a8 |
P16F88 |
Sep 26, 2013 |
21679 |
gateway-4.0a8.hex |
421 |
4.0a9 |
P16F88 |
Oct 6, 2013 |
22079 |
gateway-4.0a9.hex |
415 |
4.0a10 |
P16F88 |
Oct 10, 2013 |
22276 |
gateway-4.0a10.hex |
437 |
4.0a11 |
P16F88 |
Oct 26, 2013 |
22313 |
gateway-4.0a11.hex |
484 |
4.0b0 |
P16F88 |
Nov 30, 2013 |
22296 |
gateway-4.0b0.hex |
457 |
4.0b1 |
P16F88 |
Dec 14, 2013 |
22337 |
gateway-4.0b1.hex |
497 |
4.0b2 |
P16F88 |
Jan 25, 2014 |
22447 |
gateway-4.0b2.hex |
422 |
4.0b3 |
P16F88 |
Feb 7, 2014 |
22603 |
gateway-4.0b3.hex |
468 |
4.0b4 |
P16F88 |
Apr 5, 2014 |
23167 |
gateway-4.0b4.hex |
455 |
4.0b5 |
P16F88 |
May 11, 2014 |
23212 |
gateway-4.0b5.hex |
786 |
Please report any problems with this firmware at the
Domotica
Forum.
OpenTherm Monitor
Operating system |
Version |
Date |
Size |
File |
Downloads |
Linux-x86 |
4.1b2 |
Jun 28, 2014 |
4765317 |
otmonitor |
501 |
Linux-armhf |
4.1b2 |
Jun 28, 2014 |
4362665 |
otmonitor.ahf |
532 |
Windows |
4.1b2 |
Jun 28, 2014 |
6538942 |
otmonitor.exe |
1020 |
Source |
4.1b2 |
Jun 28, 2014 |
277114 |
otmonitor.zip |
447 |
In case of problems with this version, older
Opentherm Monitor Beta Versions are still available.
Changes since 3.4
Firmware 4.0a2
- The message handling part of the firmware has been completely reorganized.
This makes message processing more consistent and simplifies adding special
treatment for more messages.
- To avoid accidental blacklisting of supported messages, DataID's are not
considered unsupported until the boiler responds to the message with
Unknown-DataID three times in a row.
- Exclude DataID's listed as mandatory in the opentherm specification from
ever being blacklisted, even if the boiler responds with Unknown-DataID
three times in a row.
- The gateway will autonomously generate opentherm messages towards the
boiler if no opentherm compliant thermostat is
connected.
- When the thermostat wires are short-circuited, the gateway will instruct
the boiler to start heating. This allows the gateway to be used with an
on/off thermostat.
- With boilers that do not support the remote boiler parameter DataID's (6,
48, 49, 56, and 57), the gateway will simulate at least read support. In
this case the values provided via the SH and SW serial commands are returned
to the thermostat.
- Stop sending the Celcia setpoint in DataID 9.
- New serial command 'CS' to allow manipulation of the control setpoint
being sent to the boiler in DataID 1 messages.
- New serial command 'MM' to configure the Maximum Relative Modulation Level
to send to the boiler in Write-Data requests for DataID 14. Valid values are
0 to 100. Clear the setting by specifying a non-numeric value, for example:
MM=T
- New serial command 'TQ' for buggy Remeha iSense thermostats that will not
overrule a remote setpoint by a program setpoint change if, in addition to
the program change priority bit, the manual change priority bit is also set
in a DataID 100 message.
Firmware 4.0a3
- New serial commands 'SR' and 'CR' to set and clear responses towards the
thermostat. The SR commands takes a DataID and one or two byte values to
return to the thermostat for that DataID. The 'CR' command only takes the
DataID number to clear. Examples: "SR=18:1,230", "SR=70:14", "CR=18".
Firmware 4.0a4
- Not all boilers will echo the data in write requests for message IDs
they don't support. So the old method of only storing the data bytes in
responses doesn't work so well. For write-data messages, the data is now
taken from the request.
- Initial steps at working around Remeha iSense issues.
Firmware 4.0a5
- Support for a DS18B20/DS18S20 outside temperature sensor to be connected
to the GPIO connector: pin 1: GND, pin 2: DQ, pin3 Vdd. In addition a 4k7
resistor is required between DQ and Vdd.
- LEDs flash on powerup of the gateway (after about 1 second).
Firmware 4.0a6
- Experimental Opentherm Smart Power support. With this feature you don't
need batteries in the iSense aymore for the backlight to work. There is also
an associated new LED function: "P", that will light the LED whenever the
thermostat requests a raised power level.
- New GPIO function: The GPIO pins can now be used to drive up to two more
LEDs.
- New GPIO function: Set the room setpoint to a fixed temperature based on
an input signal. For example, if your security system has an output that can
indicate when the system is armed, you can automatically lower the setpoint
when you arm the security system upon leaving the house.
- GPIO functions can be configured via serial commands: GA=# for GPIO port
A, and GB=# for GPIO port B. The following functions are available:
- No function, default for both ports on a freshly flashed chip.
- Ground - A permanently low output (0V). Could be used for a power LED.
- Vcc - A permanently high output (5V). Can be used as a short-proof power
supply for some external circuitry used by the other GPIO port.
- LED E - An additional LED if you want to present more than 4 LED
functions.
- LED F - An additional LED if you want to present more than 5 LED
functions.
- Setback, low active - Set thermostat to setback temperature when pulled
low.
- Setback, high active - Set thermostat to setback temperature when pulled
high.
- DS1820 (GPIO port B only) - Data line for a DS18S20 or DS18B20 temperature
sensor used to measure the outside temperature. A 4k7 resistor should be
connected between GPIO port B and Vcc.
The GPIO port configuration is stored in EEPROM so it will survive a power
interruption.
- New SB command to configure the setback temperature. Initial setting is
16°C. The current setting can be obtained with the 'PR=S' command. The
setback temperature is stored in EEPROM so it will survive a power
interruption.
- The 'PR=G' command has been changed to report the GPIO pin configuration
settings. The command returns two digits that indicate the configured
functions for GPIO port A and port B respectively. The operating mode of the
gateway can now be requested using the 'PR=M' command.
- Work-around many of the iSense quirks/bugs/misfeatures:
- A remote override setpoint cannot be changed
- The gateway will first cancel any existing remote setpoint before
setting the new one.
- Manual change of a remote override setpoint restarts the schedule
- When a manual change is detected, the gateway will continue to send the
override setpoint so the iSense doesn't resume the schedule.
- Program change does not override a temporary remote setpoint
- The iSense uses the previously received remote override function (MsgID
100) bitmap at the time the remote override setpoint (MsgID 9) is set. Just
like with the remote override setpoint, it doesn't update the remote override
function when it receives a new bitmap. The gateway uses the same trick as
with the remote override setpoint: After sending the new remote override
function bitmap, it cancels the remote override setpoint and sets it again.
Note that the iSense only requests the remote override function about once
every 12 minutes. So it may take that long before a remote override is fully
instated.
Note: These work-arounds will only be applied if a Remeha iSense thermostat
has been detected. So owners of other thermostats will not suffer the negative
side-effects (like temporarily canceling the remote override setpoint) of
these work-arounds.
- Auto-detect the Remeha thermostat type and apply the relevant work-arounds.
There is no more need to use the Remeha-specific TR or TQ commands. In fact,
those commands are not accepted anymore.
Note: Detection of the thermostat type (especially with a Celcia20) takes some
time, so sending a setpoint command soon after a power failure or reconnecting
the thermostat may not work correctly.
- Greately relaxed the checks performed on the received opentherm signal.
It turns out that some equipment, notably Intergas boilers, are totally
unable to meet the Opentherm specifications, especially when the flame is
on. The Opentherm specification defines that a bit should be 1ms -10%/+15%.
On an Intergas boiler they were found to frequently be almost 1ms +25%. The
gateway now accepts bits of 1ms -25%/+50%
- Due to the more relaxed timing checks, non-significant level transitions
will never be considered to be at the wrong time anymore. The definition of
Error 01 has been changed to indicate a bouncing opentherm signal, i.e. a
signal that rapidly changes several times between the two logical levels.
- Implemented the possibility to reset/reboot the gateway using the serial
command 'GW=R'.
Firmware 4.0a7
- You can use the 'PR=R' command to determine which thermostat the gateway
thinks is connected. It will report:
- Default, not a Remeha thermostat
- Remeha iSense
- Remeha Celcia20
- Other Remeha thermostat
- The IT command has been reintroduced to enable or disable the check for
a bouncing opentherm signal. Reports from users indicate that there is quite
a bit of equipment out there that apparently isn't able to produce clean
transitions. So the check is initially disabled when you flash the firmware.
Use 'IT=0' to enable it.
- Some boilers (like the Hitachi RWM-2.0FSN3E) acknowledge all opentherm
messages from the thermostat, instead of returning Unknown-DataId for messages
they don't support. This deprives the gateway from the opportunity to inject
its own messages towards the boiler.
Two new commands UI (unknown ID) and KI (known ID) have been added that let
the user configure which messages don't need to be sent to the boiler and
can be replaced by alternatives. This configuration is stored in EEPROM so
it will survive a power interruption.
Some good candidates for messages ID's that boilers don't normally have any
use for are: 9 (remote override room setpoint), 20, 21, 22 (date and time),
and 100 (remote override function). Also, if the boiler consistently returns
0 for message ID's 18 (water pressure) and/or 27 (outside temperature), it
is safe to assume it doesn't actually support those message ID's either.
Firmware 4.0a8
- New command 'PR=P' to print the current power level (low, medium, or
high) of the opentherm line between the gateway and the thermostat.
- Unset the outside temperature stored in the gateway with 'OT=99'.
Firmware 4.0a9
- Correctly display byte values above 199.
- Send the values specified by the SW and SH commands to the boiler
without waiting for the thermostat to issue a write command.
- Command confirmations report the command code and the value that was
used. For example: OT=14.865 → OT: 14.87
Firmware 4.0a10
- Run less easily into serial buffer overrun issues and don't hang up the
serial port in case it does happen. There is also a new error code 'OE' when
an overrun error happens in a command.
- PR=O reports C/T/N in lowercase when a requested setpoint override is not
yet confirmed and in uppercase once it is accepted by the thermostat.
Firmware 4.0a11
- Ignore spikes generated by what seems to be a second protocol on the
opentherm line, seen with Riello and Intergas boilers.
Firmware 4.0b0
- Don't switch to smart power if the thermostat hasn't indicated smart
power support.
- If the thermostat sends the same message repeatedly, it is probably
confused by the response it gets. Just in case the gateway is causing the
confusion, it resets itself.
- New command 'OH=1' to put the Remote Override Function flags in the high
byte as wel as the low byte of MsgID 100. Because the opentherm
specifications are confusing regarding the correct location of the flags,
the OH option is on by default.
- The 'PR=T' command now reports the state of both the IT and the OH
option.
- Improved transmit buffer administration to prevent losing track of what
to send.
- Repeat messages during thermostatless operation until an answer is
received.
- The Celcia 20 needs to be informed of a Remote Override Setpoint using
an unusual method. So far, the gateway only tried this once. If the Celcia
failed to recognize the request, the setpoint would not be changed. Now the
Celcia also gets several chances.
Firmware 4.0b1
- The gateway will now reset after the same message has been repeated for
more than 1 minute, while in 4.0b0 it would reset after 32 repeated messages.
With 4.0b0 it would also continue to reset itself every minute if the boiler
was switched off (e.g. for maintenance). Since 4.0b1 the gateway needs to
see successful communication before the communication failure detection is
enabled after a reset.
Firmware 4.0b2
- Prevent an unpowered USB->TTL serial converter from repeatedly
resetting the gateway.
- A continuous BREAK condition on the serial interface should not stop the
gateway from handling opentherm messages.
- When the boiler returns Unknown-DataID for a vendor specific message ID,
that message ID is not removed from the list of alternatives.
- Fix for a problem that under specific circumstances the gateway would
keep resetting the thermostat clock to midnight.
Firmware 4.0b3
- New command 'VS' for overriding the Ventilation Setpoint the gateway
will send to the slave. The command takes an integer argument representing a
percentage, e.g.: VS=10.
- Under certain circumstances, it could take more than half an hour before
a setpoint change would be applied on an iSense RF thermostat.
Firmware 4.0b4
- New CH command to control the CH enable status bit when overriding the
control setpoint. By default the CH enable bit is set after a CS command
with a value other than 0. With the CH=0 and CH=1 commands, the bit can be
manipulated.
- New PM command to specify a one-time priority message to be sent to the
boiler at the first opportunity. If the specified message returns the number
of Transparent Slave Parameters (TSPs) or Fault History Buffers (FHBs), the
gateway will proceed to request the TSPs or FHBs.
- The gateway will make sure detailed fault information is requested from
the boiler when it indicates a fault condition.
- Powered Opentherm converters may make the line logical high when no
thermostat is connected. The gateway now correctly recognizes that
situation. A logical low level must be detected before the thermostat is
considered to be reconnected.
- Debug information (specified with the DP command) is now also printed
after receiving an incorrect Opentherm message resulting in an error.
- After an error 2 (incorrect stopbit) or error 4 (parity error), the
actual received message is printed, preceded by an 'E'.
- The override report (PR=O) would print incorrect information after an
iSense thermostat had resumed its program or the setpoint was manually
modified on the iSense.
- Fixed the values of the boiler counters in a PS=1 report, which had been
rubbish since firmware 4.0b0.
- The gateway no longer pretends to send its own messages when the
thermostat is disconnected in monitor mode.
- Additional tweak to try and make the gateway work better with a Remeha
iSense RF thermostat.
Firmware 4.0b5
- Improved detection of unusual signals on the serial receiver. Neither a
continuous space, nor a 50Hz wave is allowed to have any significant impact
on the operation of the gateway.
|